Fire door regulations: who is responsible, what to check, and when a door has to be replaced

A plain-English guide for landlords, managing agents, building owners and anyone who has fire doors in their care. Written by people who make, fit and inspect them.

Fire door regulations: who is responsible, what to check, and when a door has to be replaced

Who is responsible for fire doors?

The Responsible Person under the Regulatory Reform (Fire Safety) Order 2005 has to keep the fire precautions in the common parts of a building, fire doors included, in working order: in a block of flats usually the freeholder, the residents’ management company or the managing agent. Flat entrance doors are within the Responsible Person’s fire risk assessment since the Fire Safety Act 2021, and the Fire Safety (England) Regulations 2022 give them duties to check those doors. Higher-risk buildings (18 metres or seven storeys and over) also have an Accountable Person under the Building Safety Act 2022.

What the law asks for

  • Fire Safety (England) Regulations 2022, Regulation 10: in buildings over 11 metres with two or more sets of domestic premises, check communal fire doors at least every three months and use best endeavours to check flat entrance doors at least every 12 months, keeping a record. In every multi-occupied residential building, give residents fire door information.
  • Regulatory Reform (Fire Safety) Order 2005: a suitable and sufficient fire risk assessment, and fire precautions kept in efficient working order and good repair.
  • Building Regulations, Approved Document B: the fire resistance needed for doors in new work and alterations.
  • BS 8214:2016: the code of practice for installing and maintaining timber fire door assemblies.

What an inspection looks for

  • Certification label or other evidence of what the door is
  • Gaps of about 2–4mm at the head and sides, and the certified gap under the door
  • Intumescent and smoke seals continuous, fixed and unpainted
  • At least three hinges, all screws tight
  • A closer that closes the door into the latch from any angle
  • Fire-rated glazing in a certified system
  • Ironmongery covered by the door’s certification
  • Frame fixed and fire stopped, signage in place, no damage

Repair or replace?

A door can be repaired when the result is still inside its certification: closers, hinges, seals, beads and glass, signage, packing and fire stopping. It needs replacing when there is no evidence of certification, the leaf or frame is damaged through, the gaps are beyond adjustment, the glazing isn’t covered, or it is the wrong rating for where it is.

How we can help

This guide is a summary to help you ask the right questions, not legal advice. Check the legislation and government guidance for your own building.